DC Power Genset
The AC/DC power supply is a power supply system developed by our company for high reliability wina and solar energy storage equipment, high sensitivity emergency power supply, high economy reserve power supply, etc.. The product is a combination of AC DC electric generator and battery energy storage systems, through energy management systems and automated controls, coupled with an intelligent op eration and maintenance monitoring cloud platform, to provide customers with one-stop, safe and reliable, cost-effective, unattended operation of power solutions.
Product Features:
AC-DC electric generator 10 energy storage, mains 10 energy storage + ac-dc electric generator and other multi-mode combinations, to adapt to various types of load (resistance, inductance, motor-borne, mixed load), it can satisfy the power supply demand of users' diversified load and has a wide range of application scenarios.
Through Yuchai's self-developed 10- motor engine control + PCS main core control algorithm and scheduling management strategy, the on-board running efficiency of the AC DC electric generator is optimized, and the fuel consumption of the electric generator is reduced, save the cost of power supply.
Through intelligent EMS automatic control, intelligent operation and maintenance monitoring cloud platform management power system to achieve unattended operation; users can monitor cloud platform APP or wechat small programs, control the operation and safety data of power supply at any time and place.
Application Areas:
DC generator type spectrum of the most comp lete, the highest efficiency, the highest power density of the product line.
DC Unit Model |
Engine Model |
Rated Power (kW/rpm) |
Peak Power (kW/rpm) |
Economic Power (kW/rpm) |
Rated Condition Power & Fuel Consumption (kWh/L) |
Minimum Fuel Consumption (g/kW-h) |
Voltage Platform (V) |
Operating Voltage (VDC) |
Engine B10 Life |
Motor Type |
Protection Grade |
Cooling Method |
Emission Standard |
YCPG550ZF-T3(Open Frame) CPG550ZS-T3(Silent Type) |
YCK16 | 400/1500 | 500/1500 | 300/1200 | 4.3 | ≤190 | 600/900 | 400~720/ 600~1000 |
≥500,000 km | Permanent Magnetism | IP67 | Liquid-Cooled | T3 |
YCPG412ZF-T3(Open Frame) YCPG412ZS-T3(Silent Type) |
YCK16 | 300/1600 | 320/1600 | 260/1250 | 4.43 | ≤190 | 620/900 | 480~720/ 600~1000 |
≥500,000 km | Permanent Magnetism | IP67 | Liquid-Cooled | T3 |
YCPG340ZF-T3(Open Frame) YCPG340ZS-T3(Silent Type) |
YCK09 | 250/1580 | 273/1900 | 161/1500 | 4.33 | ≤196 | 620/900 | 480~720/ 600~1000 |
≥1.6 million km
|
Permanent Magnetism |
IP67 | Liquid-Cooled | T3/T4 |
YCPG275ZF-T3(Open Frame) YCPG275ZS-T3(Silent Type) |
YCA08 | 200/1800 | 210/1900 | 147/1300 | 4.248 | ≤200 | 600/900 | 400~720/ 600~1000 |
≥500,000 km | Permanent Magnetism |
IP67 | Liquid-Cooled | T3 |
YCPG206ZF-T3(Open Frame) YCPG206ZS-T3(Silent Type) |
YCK05 | 150/1900 | 171/2200 | 76/1300 | 4.43 | ≤196 | 600/900 | 400~720/ 600~1000 |
≥80万公里 ≥800,000 km |
Permanent Magnetism | IP67 | Liquid-Cooled | T3/T4 |
YCPG138ZF-T3(Open Frame) YCPG138ZS-T3(Silent Type) |
YCS04 | 100/1700 | 130/2100 | 82/1400 | 4.185 | ≤198 | 600/900 | 400~720/ 600~1000 |
≥600,000 km | Permanent Magnetism | IP67 | Liquid-Cooled | T3/T4 |
YCPG100ZF-T3(Open Frame) YCPG100ZS-T3(Silent Type) |
YCS04 | 75/1700 | 95/2000 | 95/1500 | 4.17 | ≤198 | 600/900 | 400~720/ 600~1000 |
≥600,000 km | Permanent Magnetism | IP67 | Liquid-Cooled | T3/T4 |
YCPG90ZF-T3(Open Frame) YCPG90ZS-T3(Silent Type) |
YCY24 | 65/2100 | 74/2300 | 37/1600 | 3.89 | ≤207 | 600/900 | 400~720/ 600~1000 |
≥500,000 km | Permanent Magnetism | IP67 | Liquid-Cooled | T3/T4 |
YCPG35ZF-T3(Open Frame) YCPG35ZS-T3(Silent Type) |
YCF30 | 30/2200 | 35/2200 | 27/1400 | 3.45 | ≤220 | 600/900 | 350~750/ 600~1000 |
≥500,000 km | Permanent Magnetism | IP67 | Liquid-Cooled | T3/T4 |
Diesel Reservoirs should be used for power applications:
YCPGES-75-50(50KW/75kWh) |
YCPGES-150-100(100KW/150kWh) |
YCPGES-225-150(150KW/225kWh) |
YCPGES-300-200(200KW/300kWh) |
Diesel Reservoirs should be used for power applications | ||||||
Model | YCPG210GZS-T4 | YCPG318GZS-T4 | YCPG530GZS-T4 | YCPG693GZS-T4 | Note | |
DC Gensets |
Rated power(kW) | 60 | 90 | 150 | 200 | |
Standby power(kW) | 66 | 99 | 165 | 210 | ||
Maximum power generation efficiency (kWh/L) | 4.06 | 4.185 | 4.43 | 4.248 | ||
Engine Model/Fuel | YCY240-61/Diesel oil | YCS04180-68/Diesel oil | YCK05240-60/Diesel oil | YCA08300-T400/Diesel oil | ||
Cylinder number - Bore X Stroke(mm) | 4-85X104 | 4-105X120 | 4-110X135 | 6-110X132 | ||
Displacement(L) | 2.36 | 4.156 | 5.132 | 7.527 | ||
Motor Type | Permanent magnet synchronous motor | |||||
Working Voltage(Vdc) | 576/400~720 | 576/400~720 | 600/400~720 | 600/400~720 | ||
Motor Rated Power/Speed(kW/rpm) | 65/2100 | 100/1500 | 160/1600 | 200/1600 | ||
Motor peak power/speed(kW/rpm) | 80/(2100~3000) | 135/(1500~3000) | 200/(1600~2500) | 240/(1600~2500) | ||
Motor Maximum Speed(rpm) | 3000 | 3000 | 2500 | 2500 | ||
Motor/controller protection level | IP67 | IP67 | IP67 | IP67 | ||
Motor and controller cooling method | 液冷 | |||||
Energy Storage Systems |
Battery capacity(kWh) | 120 | 180 | 300 | 400 | Lithium iron phosphate |
Rated power(kW) | 80 | 120 | 200 | 267 | Continuous | |
Peak power(kw) | 88 | 132 | 220 | 294 | ||
System Output |
Rated Power(kW) | 140 | 210 | 350 | 467 | |
Continuous power(kW) | 140 | 210 | 350 | 467 | Energy storage lasts 1.5 hours | |
Peak Power(kW) | 154 | 231 | 385 | 504 | 1 minute | |
Rated output voltage | DC: 600/720Vdc AC: 380/400Vac |
|||||
Rated AC Output Frequency(Hz) | 50/60 | |||||
Controller and communication port | 1 set each for unit and energy storage, 2 sets total/RS485, CAN, ETH, 4G | |||||
System operating conditions | Operating Ambient Temperature | -20℃~45℃ | ||||
Storage Ambient Temperature | -30℃~55℃ | |||||
Operating Relative Humidity | 0~95% | |||||
System noise | ≤75dB | |||||
Protection class | IP54 |